Simulink model of transformer differential protection using phase angle difference based algorithm
Küçük Resim Yok
Tarih
2020
Yazarlar
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Institute of Advanced Engineering and Science
Erişim Hakkı
info:eu-repo/semantics/openAccess
Özet
An application of phase-angle-difference based algorithm with percentage differential relays is presented in this paper. In the situation where the transformer differential relay is under magnetizing inrush current, the algorithm will be utilized to block the process. In this study, the technique is modeled and implemented using Simulink integrated with MATLAB. The real circuit model of power transformer and current transformers are considered in the simulation model. The results confirmed the effectiveness of the technique in different operation modes; such as, magnetizing inrush currents, current transformers saturation and internal transformer faults. © 2020, Institute of Advanced Engineering and Science. All rights reserved.
Açıklama
Anahtar Kelimeler
Differential relay; Inrush current; Internal fault; Phase angle difference
Kaynak
International Journal of Power Electronics and Drive Systems
WoS Q Değeri
Scopus Q Değeri
Q3
Cilt
11
Sayı
2